MPX Float Sensor

$1,250.00

Monitor liquid levels with a float level sensor and a ControlByWeb® module. Receive text/email alerts when a user-specified level is reached. Log and graph a tank’s level data over time.

Max Length: Up to 32ft. (175.25m)

Modbus RS-485

4-20mA, 2-Wire

External Power: 12-24 VDC

Frequently Bought Together

Fast, secure checkout!

  • Most products ship same day
  • 30-day return policy
  • Responsive technical support
Call to Order

Float Sensor – Liquid Level Switch

Monitor liquid levels with a float level sensor and a ControlByWeb® module. Receive text/email alerts when a user-specified level is reached. Log and graph a tank’s level data over time.

How do Float Sensors Work

Magnetostrictive liquid level sensors consist of a float that moves up and down a stem, or rod. The float contains a permanent magnet, and the stem houses a wire waveguide that creates a magnetic field, making it possible to detect the floats position on the stem.

An electrical pulse travels down the waveguide, magnetizing it. When the pulse meets the magnetic field from the float, a vibration, also called a strain pulse, travels back to the sensor housing.

The Float sensor or liquid level switch then measures the difference in time between the initial pulse, and the strain pulse, giving it an accurate and continuous reading of the tank’s current level.

This Float Level Sensor uses Float Waves to monitor tank levels

Liquid Types

Float Level Sensors work well with clean and dirty liquids, as they are customizable for almost any application.

Clean Liquid Float Level Sensor
Dirty Liquid Float Level Sensor
Corrosives Float Level Sensor

Float Sensor Benefits

  • Simple measurement principle.
  • Provide the most reliable and accurate method of level monitoring.

Sensor Ranges

  • MPX float sensors are customizable for monitoring up to 32 ft with multiple float sensors.

Sensor Accuracy

  • Sensors are accurate within 0.05% of its detected range.

Recommended Installation

Top of Tank

Carefully lower the MPX Float Sensor into the tank, then secure the sensor to the tank. If the floats don’t fit through the mounting hole, remove the floats and connect the floats from the inside of the tank after the stem has been lowered through the mounting hole.

This liquid level switch uses Float Waves to monitor tank levels

Sensor Specifications

PERFORMANCE
  • Max Length: Up to 32ft. (175.25m)
  • Accuracy: Greater of ±0.04 in. (±1mm)
    or 0.05% of full range
  • Resolution: Modbus ±0.04 in. (±1mm)
    4-20 mA: 14 bit DAC
  • Operating Temp: -40°F to 180°F (-40°C to 80°C)
OUTPUTS
  • Modbus RTU (RS-485) with Temperature output
  • 4-20mA, 2-Wire
  • Dual 4-20mA (Loop-Powered 3 wire)
  • Call to configure
ELECTRICAL
  • External Power: 12-24 VDC
APPROVALS
  • Protection Rating: NEMA 4X, IP65
  • Certifications: Class 1 Division 1 Groups C & D, Class 1 Zone 1, Class 1 Zone 2
INTERNET CONNECTIVITY
  • NO CLOUD NEEDED! Remote connection available with ControlByWeb devices (see below)
PROGRAMMING
  • Automatic programming via ControlByWeb device
SENSOR MATERIALS
  • Housing: Cast aluminium, epoxy coated
  • Cable Length: Customizable
  • Dual-Level: Monitor two liquid levels with a single sensor
ENVIRONMENTAL
  • Operating Temp: -40°C to 85°C
INSTALLATION
  • Top of tank | Simple to install and program